The growing share of Inverter-Based Resources (IBRs) is changing the operation of modern Active Distribution Networks (ADNs), raising concerns for grid stability, protection, and reliability. In this paper, we investigate the dynamic behavior of a Medium-Voltage (MV) portion of an ADN during the transition from grid-connected to islanded operation. The study considers a Grid-Following (GFL) converter and Synchronous Generators (SGs) operated under two distinct regulation modes: a fixed-setpoint, non-regulating condition representative of present-day distribution networks, and an active frequency/voltage-regulating condition representative of SGs equipped with governor and AVR control. Detailed electromagnetic transient (EMT) models of both technologies have been developed in DIgSILENT PowerFactory that quantifies the sensitivity of island persistence to SG regulation mode and inertia. The results show that when DERs operate at a fixed power setpoint, the risk of forming a sustained, undetected electrical island is limited, since the isolated network drifts out of the protection thresholds within tens of seconds. Conversely, enabling frequency and voltage regulation on the SGs is sufficient to sustain an unintentional island indefinitely without triggering conventional protection, regardless of system inertia.
Unintentional islanding is defined as the condition in which a section of the power grid continues to be energized by distributed generators after disconnection from the utility grid, for example, due to a fault. This situation remains a significant protection challenge in microgrids with high penetration of inverter-b...
Elijah Gbenga Osunkentan, R. D. dos Santos, Adedeji Adeyemi· Discover Electronics· 0 citations
The increasing penetration of distributed generation (DG) based on renewable energy sources is transforming passive radial distribution networks into active, bidirectional microgrids. While this transition improves efficiency, reliability and environmental performance, it introduces the risk of unintentional islanding,...
Mangesh R. Shelke, Santosh S. Raghuwanshi· International journal of com...· 0 citations
The increasing usage of Renewable Energy Sources (RES), which are typically interfaced with the grid as Inverter-Based Resources (IBRs), is leading to the formation of Microgrids (MGs) and Networks of MGs (NMGs). MGs and NMGs can operate autonomously in islanded mode. However, there are prevailing operational challenge...
Ahmed Saad Al-Karsani, Maryam Khanbaghi· IEEE Access· 0 citations
The increasing replacement of synchronous generators (SGs) by grid-following (GFL) and grid-forming (GFM) inverters is reshaping the dynamic bus characteristics of modern power systems. This transition makes a fixed ideal-voltage-source representation of the upstream main grid increasingly inadequate, especially when t...
Over the years, Dominion Energy Virginia (DEV) has experienced recurring power quality disturbances, including voltage and power oscillations, particularly in areas with significant inverter-based generation. While these phenomena suggest a potential relationship to system strength, no definitive correlation has yet be...
Mohammed N. Khamees, G. Ilunga, Zhong-Xia Zhang et al.· arXiv.org· 0 citations