Skip to content
Conference

Topology-Aware Multi-Task Graph Learning for Fault Diagnosis in PV-Integrated Distribution Networks with Missing Measurements

Aug 2026 · 2026 6th International Conference on Mechanical, Electronics and Electrical and Automation Control (METMS) · pp. 1148-1153 · 0 citations · 16 references

Abstract

Fast and reliable fault diagnosis is a prerequisite for restoring service in active distribution networks, where distributed photovoltaic (PV) generation and sparse sensing complicate protection decisions. Existing learning-based methods degrade sharply when measurements are missing at test time: zero-filled inputs are indistinguishable from genuine deep voltage sags, and graph models built on the full feeder dilute informative readings across many unmeasured buses. This paper presents TMGN, a topology-aware multi-task graph network that performs fault-type identification and section localization with one model; it propagates measurements over a Kron-style reduced measurement graph weighted by electrical distance, and combines a learnable missing token with mask-randomized training. Because every graph node carries a measurement and missingness is encoded explicitly, the learned representation degrades gracefully as observability drops. On a simulated IEEE 33-bus feeder with three PV plants, ten fault types, and eight sections, TMGN matches the strongest single-task baselines at the nominal 20% missing rate (localization accuracy within 0.6 points) and retains $\mathbf{5 2 . 7 6 \%}$ localization accuracy at $\mathbf{6 0 \%}$ missing, 4.7 points above the best baseline, across five random seeds.

View source

We use cookies to run the site and, with your consent, for analytics and to show ads. See our Cookie Policy.