Skip to content
Open access

Multi-modal sensing and pulse sequence analysis for single-source and dual-source partial discharge diagnosis in transformers under complex operating conditions

Jul 2026 · Measurement science and technology · Vol 37, pp. 326107 · 0 citations · 39 references
Physics

Abstract

Transformer partial discharge (PD) diagnosis may simultaneously face narrowband interference under undersampling conditions, limited fault samples, class imbalance, and multi-source signal mixing. To address these issues, this paper proposes a multi-modal pulse-sequence-based diagnostic framework using synchronized Optical, ultra-high-frequency (UHF), and high-frequency current transformer (HFCT) measurements, and experiments are conducted on a laboratory platform with five typical PD defect models of oil-immersed transformers. For front-end signal processing, a spectral dilation and linear trend replacement (SDLTR) method is proposed to suppress narrowband interference in HFCT signals while preserving the original pulse timing and amplitude characteristics. On this basis, conventional single-sensor pulse sequence analysis (PSA) is extended to an adaptive tri-modal PSA fusion scheme for single-source PD classification. By constructing the temporal union of synchronized Optical, UHF, and HFCT pulse streams and using expert-weighted decision fusion, the proposed method exploits cross-modal complementarity and enlarges the effective sample set. Under class-imbalanced conditions, the four-pulse-based PSA6 fusion scheme achieves an accuracy of 95.47% and a Macro-F1 of 95.17%. For dual-source PD mixtures, an adaptive cascaded decoupling framework (ACDF) is further proposed by combining class-level precision-weighted fusion, an adaptive confidence boundary, and two-stage dominant-source stripping based on PSA6 and PSA4. The proposed framework produces zero false decisions in single-source verification and correctly identifies both PD sources in all ten dual-source combinations. These results demonstrate that the proposed framework provides an effective and practical solution for transformer PD diagnosis under complex operating conditions.

Read PDF

Similar papers

Open access Sep 2026

Few-Shot Fault Diagnosis of On-Load Tap Changers Based on a Multi-Source Cross-Sensor Prototype Adaptation and Dual-Prototype Fusion Network

An on-load tap changer (OLTC) is a key electromechanical switching device for transformer on-load voltage regulation, and its mechanical condition is closely related to equipment reliability. Vibration signals are sensitive to sensor location, so the same fault may exhibit different responses at different locations, wh...

Zhi-Xin Chen, Chen-Lei Liu, Tian-Yu Duan et al. · 0 citations
Open access Sep 2026

Intelligent UHF Sensor-Based Partial Discharge Fault Diagnosis in GIS Using a Temporal-Frequency Dual-Branch Stochastic Configuration Network

Gas-insulated switchgear (GIS) is an important component of power transmission systems. Accurate partial discharge (PD) pattern recognition is a key requirement for identifying internal insulation defects within the equipment. However, ultra-high-frequency (UHF) PD pulse sequences produced by different insulation defec...

Ming-Yuan Hu, Jing-Wen Liu, Bao-Long Yu et al. · 0 citations
Review Open access Sep 2026

Embedded AI/ML Systems for Partial Discharge Monitoring: A Review

Online partial discharge monitoring is increasingly complementing periodic offline testing in medium-voltage switchgear, particularly through the use of embedded and edge-computing platforms. This review critically examines systems based on artificial intelligence and machine learning for partial discharge detection an...

Bartosz Owczarczuk, B. Dziadak, Jacek Starzyński · 0 citations
Open access Aug 2026

The Hybrid DBSCAN-Transformer Framework for High-Precision Phase Fraction Measurement in Low-Energy Gamma Flowmeter

Multiphase flow metering is widely employed in the oil and gas industry, particularly for measuring gas-liquid-solid multiphase flow at drilling outlets. Low-energy gamma flowmeters offer relatively high metering accuracy, with phase fraction errors for gas, liquid, and solid typically within ±10%. However, in practica...

Yibo Huang, Mingyang Liu, Li-Jing Fan et al. · 0 citations