Skip to content

A Novel Differential Protection Method for Current Limiting Control of Non‐Isolated DCTs in Multi‐Voltage Level DC Grids

Sep 2026 · International journal of circuit theory and applications · 0 citations · 25 references

Abstract

The DC transformer (DCT) is critical equipment used to interconnect DC grids with different voltage levels. Unlike AC transformers, DCT fault behavior is significantly affected by its internal active components and topology, making conventional differential protection methods inadequate. This paper proposes a novel differential protection method for the non‐isolated DC modular multilevel transformer (DCMT), which employs the AC and DC components of the DCMT current to establish composite differential criteria. First, a fault analysis model of a multi‐voltage level DC grid with DCMT is established, and fault currents at different fault locations in the DCMT can be quantitatively analyzed. Subsequently, the differential current characteristics of the DCMT under various fault conditions are analyzed, revealing the limitations of traditional differential protection methods. On this basis, a composite criterion is proposed to identify internal and external faults. Furthermore, considering the impact of fault severity on fault identification, an adaptive strategy for DCMT is designed using the current phase‐plane, which enhances the sensitivity of turn‐to‐turn fault (TTF) identification. Finally, a simulation model of a multi‐voltage level DC grid containing DCMT is constructed using the PSCAD/EMTDC simulation platform to verify the effectiveness and correctness of the proposed method.

View source

Similar papers

Open access Aug 2026

Dynamic Fault Detection and Protection Strategies for Medium-Voltage Networks Supplied by Grid-Forming Inverter Sources

In recent years, high penetrations of inverter-based resources are posing significant challenges to the medium-voltage networks, in which protection schemes based on high fault currents and unidirectional power flow may not perform as expected. This paper proposes a dynamic fault-detection and relay-coordination scheme...

Muhammad Abdul Rauf, Munira Batool, I. Madni · 0 citations
Open access Sep 2026

Design of a comprehensive protection algorithm for fault detection, classification, and location in high voltage direct current transmission lines connected to wind farms based on local terminal measurements

With the increasing adoption of bipolar high-voltage direct-current (HVDC) transmission lines for wind farm integration, the development of fast, accurate, and communication-independent protection schemes has become a critical technical requirement. This paper proposes a comprehensive protection algorithm within an int...

Mahyar Abasi, Vahid Davatgaran, Morteza Azizi · 0 citations
Review Open access 2026

A Review of DC Fault Current Limiters for HVDC Systems: Classification and Design Considerations of Non-Superconducting Topologies

The rapid expansion of voltage source converter-based high voltage DC grids has made DC fault protection a critical research priority, due to low network impedance and the absence of natural current zero crossings. DC fault current limiters have emerged as an effective means of suppressing the rapid rise of fault curre...

M. Mohammadi, Saeed Norouztamar, Hossein Iman-Eini et al. · 0 citations
Open access Sep 2026

Improved VDCOL Control Method of Multiple HVDC Systems for Commutation Failure Mitigation

The voltage-dependent current order limiter (VDCOL) is an important link in the current control of HVDC systems. However, due to the fixed startup voltage threshold and the fixed slope of the characteristic curve, its control performance in complex multiple HVDC systems needs to be improved. This paper first analyzes t...

Yan-Qi Hou, Da-zhou Zhou, Kuan Li et al. · 0 citations
Open access Sep 2026

Voltage–Current Curve-Based Line Protection for Renewable Energy Systems with Grid-Forming Inverters

The increasing penetration of inverter-based renewable energy resources is reshaping transmission-line fault characteristics and weakening protection criteria designed for synchronous-generator-dominated grids. This paper proposes an internal-fault identification scheme based on voltage–current coupling characteristic...

Long-Fei Ren, Xiao He, Wei-Zhen Li et al. · 0 citations
Preprint Aug 2026

Non-Blocking Fault Current Limiting Control of Half-Bridge MMCs for MTDC Transmission

A key protection requirement in multiterminal HVDC (MTDC) transmission systems is to selectively isolate faulted areas using DC circuit breakers (DCCBs) during DC faults while keeping the rest of the systems in operation. However, in MTDC systems using half-bridge modular multilevel converters (HB-MMCs), the lack of in...

Peng-Xiang Huang, Shahil Shah · 0 citations