The hybrid operation of grid-following (GFL) and grid-forming (GFM) renewable energy units can lead to phase-reference inconsistencies and distorted transient impedance trajectories, which in turn cause maloperation or failure-to-operate of conventional distance protection. To address this issue, this paper proposes a novel distance protection method based on transient impedance fitting. First, a dynamic phase transformation is applied to map the currents of GFL units into a unified reference frame, enabling consistent representation of heterogeneous currents from the hybrid renewable energy station. Second, a transient equivalent impedance model is established based on the transient voltage-current relationship of the transmission line, revealing the influence mechanisms of the rates of change in current amplitude and phase angle on the transient additional impedance. Finally, the magnitude of the transient impedance within a short post-fault data window is selected as the fitting object. The least-squares method is employed to extract the linear fitting slope and intercept, which characterize the evolution trend and initial position of the transient impedance trajectory, respectively, thereby forming the criteria for distinguishing internal and external faults. Simulation results demonstrate that the proposed method correctly identifies fault sections under various fault locations, transition resistances, and renewable power output conditions, with the protection decision completed within 15 ms. The proposed method effectively overcomes the susceptibility of conventional distance protection to maloperation and failure-to-operate in scenarios with high renewable energy penetration.
The increasing penetration of inverter-based renewable energy resources is reshaping transmission-line fault characteristics and weakening protection criteria designed for synchronous-generator-dominated grids. This paper proposes an internal-fault identification scheme based on voltage–current coupling characteristic...
Long-Fei Ren, Xiao He, Wei-Zhen Li et al.· Electronics· 0 citations
The increasing replacement of synchronous generators (SGs) by grid-following (GFL) and grid-forming (GFM) inverters is reshaping the dynamic bus characteristics of modern power systems. This transition makes a fixed ideal-voltage-source representation of the upstream main grid increasingly inadequate, especially when t...
This paper examines the transient power-angle stability of grid-forming converters (GFMs) subjected to grid faults. Existing studies commonly simplify the network as a purely inductive line and use ideal fault assumptions, which makes it difficult to describe how practical fault conditions influence power transmission...
X.-Y. Deng, X.-L. Zhu, Y. Hu et al.· Advanced Electromagnetics· 0 citations
With the increasing penetration of inverter-based resources (IBRs), maintaining converter-driven stability has become a critical challenge. Static synchronous compensators (STATCOMs) are widely deployed for voltage regulation through rapid injection or absorption of reactive power, making their capability crucial in IB...
JooYong Jung, NamKyu Kim, Soo Hyoung Lee et al.· Electronics· 0 citations
: The deployment of grid-forming converters (GFMC) in weak-grid renewable energy stations can provide voltage support for grid-following converters (GFLC). However, the coupling between the two types of converters may cause the voltage-support capability of the GFMC to be constrained by its overcurrent capacity during...
Yuxuan Chen, Ying-Qi Yi, Meng-Yan Ni et al.· Energy Engineering· 0 citations
With the large-scale integration of high-voltage direct-current (HVDC) transmission systems, the receiving-end AC grid exhibits weak voltage-support capability. Consequently, grid-forming (GFM) battery energy storage converters are required to satisfy both current-limiting and voltage-support requirements during fault...
Pu Liu, Zhao-Fan Wang, Yong-Peng Shen et al.· Electronics· 0 citations